Ten records went into the catalog on 25 November, and nine of them are below: five in Mitel’s MiCollab conferencing component, one in Juniper Session Smart Conductor, three in Danfoss AK-SM 800A building controllers. The tenth is CVE-2026-133469 in Vates Xen Orchestra. Seven of the nine here carry a 28 November due date and two run to 9 December 1. I would start with the Juniper entry, because Juniper reports at least one malicious exploitation of it 2.

A root shell from a crafted minion ID

CVE-2026-103406 is an OS command injection in the AutomatedProvisioner, the part of Session Smart Conductor that handles key management. A crafted salt minion ID reaches a command line as root 3, and the CVSS 3.1 vector shows no privileges and no user interaction 2. Juniper scores it 9.8 2, and NVD carries the same score from Juniper as the CNA 3. The fixed releases are 7.0.5, 7.1.7 and 7.2.3 2.

The bulletin covers Session Smart Router and Conductor, and the KEV entry names both products. NVD’s affected products table lists Conductor alone 23. A conductor is its own appliance, separate from the routers it provisions, so a scan that finds one has not found the other.

Juniper revised the bulletin on 24 November to record that at least one instance of malicious exploitation had been reported to its SIRT, and the bulletin states that no workaround covers the full set of issues in that release 2. That note is why I would not park this one behind the conferencing work.

Five flaws in one conferencing component

Mitel issued MISA-2026-0012 on 16 November and updated the CVE numbers in revision 2.0 on 24 November 4. All five sit in the Audio, Web and Video Conferencing component of MiCollab 10.3 (10.3.0.18) and earlier 4.

CVE-2026-133323 is a blind command injection from insufficient parameter sanitization, scored 10.0. CVE-2026-133303 is XML injection through insufficient parameter validation that runs commands when malicious content already sits on the system, scored 9.0 4. Neither needs an authenticated session, and the second depends on content staged in advance. The other three widen the entry: CVE-2026-133275 is an arbitrary file upload at 5.3, CVE-2026-133324 an authentication bypass at 5.3, and CVE-2026-133311 unauthorized access to sensitive information that requires a system-generated identifier, at 5.9 4.

Mitel’s own note is that exploiting the set together amplifies the impact, which makes one component with five records a better unit of work than five tickets 4. A patch exists for release 10.3 (10.3.0.18), and restricting external access to AWV is the listed interim step 4. Four of the five carry the 28 November due date; CVE-2026-133311 runs to 9 December 1.

Mitel’s fallback is to cut external access to AWV, and no version list shows which address that component answers on, so the first check on a phone system is whether AWV answers to the internet.

Three Danfoss controller flaws, two of them from 2023

Danfoss AK-SM 800A is a refrigeration and building controller that sits on an operations network. CISA added three records for the series in the 25 November wave, and Danfoss published two of them in 2023.

CVE-2023-25914 is a path traversal through the XML interface that reads system files, and Danfoss scores it 7.5 5. NVD’s record for it describes authenticated attackers and carries a primary 8.8 6. CVE-2023-25915 is command execution after improper input validation, and it needs an authenticated session 7. Three scores exist for that one: Danfoss published 9.8 in DSA-2023-08-01, NVD carries 8.8, and the DIVD score as CNA is 9.9 57. The NVD and DIVD vectors differ only on scope, changed for DIVD and unchanged for NIST, and the base scores follow from that.

CVE-2025-41450 is the newer of the three: an authentication bypass that Danfoss classifies as CWE-305, where an attacker can generate a web report exposing internal IP addresses, usernames and store names 8. NVD scores it 7.5 and Danfoss scores it 8.2 89.

The fix levels are the part worth carrying into a ticket. DSA-2023-08-01 points at firmware 3.3 for the two older records, and DSA-2025-03-01 points at 4.2 for the newer one 58. Firmware 4.2 clears all three. Danfoss fixed the 2023 pair in 3.3, so a controller on 3.3 still carries the 2025 flaw.

What the handoff looks like

What I send the teams that own these systems is two fixed versions, a patch and a due date: 7.2.3 for the conductor, the MiCollab patch for release 10.3, and 4.2 for the controllers. The check is the part they can start without reading any of the advisories, and the seven records due on 28 November make the order matter.


  1. Cybersecurity and Infrastructure Security Agency. (2026). CISA catalog of known exploited vulnerabilities (Version 2026.11.25) [Data set]. https://www.cisa.gov/sites/default/files/feeds/known_exploited_vulnerabilities.json ↩︎ ↩︎

  2. Juniper Networks. (2026, November 24). 2026-10 on-demand security bulletin: Session Smart Router and Session Smart Conductor: Multiple internally discovered vulnerabilities resolved (JSA112183). Juniper Support Portal. https://supportportal.juniper.net/s/article/2026-10-On-Demand-Security-Bulletin-Session-Smart-Router-and-Session-Smart-Conductor-Multiple-internally-discovered-vulnerabilities-resolved ↩︎ ↩︎ ↩︎ ↩︎ ↩︎ ↩︎

  3. National Institute of Standards and Technology. (2026, October 28). CVE-2026-103406 detail. National Vulnerability Database. https://nvd.nist.gov/vuln/detail/CVE-2026-103406 ↩︎ ↩︎ ↩︎

  4. Mitel. (2026, November 24). Mitel product security advisory MISA-2026-0012: MiCollab multiple vulnerabilities (Rev. 2.0). https://www.mitel.com/support/security-advisories/mitel-product-security-advisory-misa-2026-0012 ↩︎ ↩︎ ↩︎ ↩︎ ↩︎ ↩︎

  5. Danfoss. (2023, August 21). DSA-2023-08-01: Insufficient restrictions and input sanitization exist in Danfoss AK-SM 800A. https://www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2023-08-01/ ↩︎ ↩︎ ↩︎

  6. National Institute of Standards and Technology. (2023, August 21). CVE-2023-25914 detail. National Vulnerability Database. https://nvd.nist.gov/vuln/detail/CVE-2023-25914 ↩︎

  7. National Institute of Standards and Technology. (2023, August 21). CVE-2023-25915 detail. National Vulnerability Database. https://nvd.nist.gov/vuln/detail/CVE-2023-25915 ↩︎ ↩︎

  8. Danfoss. (2025, March 24). DSA-2025-03-01: Improper authentication vulnerability in Danfoss AK-SM8xxA Series. https://www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2025-03-01/ ↩︎ ↩︎ ↩︎

  9. National Institute of Standards and Technology. (2025, May 8). CVE-2025-41450 detail. National Vulnerability Database. https://nvd.nist.gov/vuln/detail/CVE-2025-41450 ↩︎